Blue flanged pressure safety valve installed on plant pipework, with its tag and seal wire

PRV, PSV & PRD testing

Lifts at set. Seats tight.

NATA accredited set pressure and seat tightness testing of pressure relief and safety valves to AS 1271 and API 527. On our workshop bench in Darwin with water or nitrogen, or on site from our mobile nitrogen unit.

  • NATA 0–100,000 kPa
  • AS 1271
  • API 527
  • Flanged & screwed
  • Water or nitrogen
  • Mobile test unit
  • ASME PRD technicians

Do you need it?

The last line of protection. Prove it still works.

A relief valve stops overpressure when every other control has failed. A test shows whether it still lifts at its set pressure and reseats without leaking. If you run vessels, air receivers, compressors or process plant, your inspection plan and AS/NZS 3788 set how often each valve is tested.

Valves change in service. Springs relax, seats wear and deposits build up, so the lift point drifts. A valve that weeps below set loses product and can't be trusted to reseat after a lift. We test it as found, reset it if it's out, and certify it as left.

Last line of protection

When every other control fails, the relief valve is what stops the overpressure.

Set pressure drifts

Testing shows where the valve really lifts, not where the nameplate says it should.

Leaking seats cost

A weeping seat loses product and may not reseat properly after a lift.

NATA accredited · No. 12303

Water or nitrogen, inside our NATA scope.

We test with the medium that suits the valve's service. Both are within our NATA accreditation from 0 to 100,000 kPa.

Hydrostatic · water

Liquid service

Set pressure and seat tightness tested with water on the bench.

NATA: AS 1271 s2.6 and API 527 cl 4

Pneumatic · nitrogen

Gas and vapour service

Set pressure, then seat tightness by bubble count.

NATA: AS 1271 s3.4 and API 527 cl 2 & 5

s2.6 · s3.4AS 1271Safety valves: hydrostatic and pneumatic tests
cl 2, 4 & 5API 527Seat tightness of pressure relief valves
Range0–100,000kPa, water or nitrogen

Workshop test bench

Metrus PK2 bench, DN25 to DN400.

Our Metrus PK2 test bench in the Darwin workshop clamps flanged valves from DN25 to DN400 (1 to 16 inch) and takes screwed valves too. Set pressure and seat tightness are tested with water or nitrogen and read on calibrated gauges.

The standard claw clamps the inlet flange on a 300 mm reach and suits most valves. The T-claw has a tighter 220 mm reach and holds about double the pressure on the same flange size. The limits below are the maximum test pressure for each flange size.

DN25 · 1 in100,000kPa, standard claw. T-claw: 100,000 kPa
DN32100,000kPa, standard claw. T-claw: 100,000 kPa
DN40 · 1½ in47,000kPa, standard claw. T-claw: 94,000 kPa
DN50 · 2 in27,000kPa, standard claw. T-claw: 54,000 kPa
DN6518,000kPa, standard claw. T-claw: 36,000 kPa
DN80 · 3 in12,500kPa, standard claw. T-claw: 25,000 kPa
DN100 · 4 in9,000kPa, standard claw. T-claw: 18,000 kPa
DN125 · 5 in6,000kPa, standard claw. T-claw: 12,000 kPa
DN150 · 6 in4,400kPa, standard claw. T-claw: 8,800 kPa
DN175 · 7 in3,300kPa, standard claw. T-claw: 6,700 kPa
DN200 · 8 in2,500kPa, standard claw. T-claw: 5,000 kPa
DN250 · 10 in1,400kPa, standard claw. T-claw: 2,800 kPa
DN300 · 12 in1,200kPa, standard claw. T-claw: 2,400 kPa
DN350 · 14 in800kPa, standard claw. T-claw: 1,600 kPa
DN400 · 16 in700kPa, standard claw. T-claw: 1,400 kPa

Maximum test pressure by flange size, from the bench’s clamping plate.

How a test runs

As found, adjusted, tested, certified.

  1. 01

    Record

    Nameplate, set pressure and condition as received.

  2. 02

    As found

    Pressure raised until the valve lifts. Set pressure recorded.

  3. 03

    Adjust

    Reset to the nameplate by our PRD technicians if it’s out.

  4. 04

    Seat tightness

    Held below set and checked for leakage.

  5. 05

    Certify

    As-left results on a certificate for every valve.

Mobile test unit

We bring the test bench to your site.

Our mobile test unit runs on nitrogen and tests flanged and screwed valves where they’re removed, read on a calibrated digital master gauge. No freight to a workshop and back.

Seat tightness by bubble count

With the valve held below its set pressure, the outlet is piped to a tube under water and the bubbles are counted for a minute. The count is checked against the API 527 limit for the valve’s set pressure and orifice. Soft-seated valves are tested to zero bubbles.

DITS technician at the mobile relief valve test unit in the back of a service ute, with a digital master gauge on top
Our mobile nitrogen test unit, ready in the ute.

Valves we test

Flanged and screwed, process and utility.

Workshop

Flanged PSVs

Process and plant safety valves, DN25 to DN400 on the bench.

Workshop or site

Screwed PRVs

Air receivers, compressors and small vessels.

People

ASME PRD technicians

Certified for the inspection, testing, maintenance and certification of pressure relieving devices.

If it fails

Replacement valves

We can supply a replacement valve or spring so the equipment goes back into service.

What you get

A certificate for every valve, as found and as left.

  • As-found and as-left set pressure
  • Seat tightness result
  • A NATA-endorsed certificate for tests within our scope
  • Master gauge ID and calibration details
  • A clear pass, reset or fail call

What we need from you

Two things.

  • A valve list: tag, size, connection and set pressure
  • The service: gas, vapour or liquid

Pressure testing the system as well? See hydrostatic testing.

Cover of the DITS PRV and PSV testing brochure

Brochure

PRV and PSV testing

Relief valve testing on the workshop bench or our mobile unit.

4 pages · PDF 0.8 MB

View Download PDF

Get in touch

Relief valves due for testing?

Swift reporting, round the clock.