PRV, PSV & PRD testing
Lifts at set. Seats tight.
NATA accredited set pressure and seat tightness testing of pressure relief and safety valves to AS 1271 and API 527. On our workshop bench in Darwin with water or nitrogen, or on site from our mobile nitrogen unit.
- NATA 0–100,000 kPa
- AS 1271
- API 527
- Flanged & screwed
- Water or nitrogen
- Mobile test unit
- ASME PRD technicians
Do you need it?
The last line of protection. Prove it still works.
A relief valve stops overpressure when every other control has failed. A test shows whether it still lifts at its set pressure and reseats without leaking. If you run vessels, air receivers, compressors or process plant, your inspection plan and AS/NZS 3788 set how often each valve is tested.
Valves change in service. Springs relax, seats wear and deposits build up, so the lift point drifts. A valve that weeps below set loses product and can't be trusted to reseat after a lift. We test it as found, reset it if it's out, and certify it as left.
Last line of protection
When every other control fails, the relief valve is what stops the overpressure.
Set pressure drifts
Testing shows where the valve really lifts, not where the nameplate says it should.
Leaking seats cost
A weeping seat loses product and may not reseat properly after a lift.
NATA accredited · No. 12303
Water or nitrogen, inside our NATA scope.
We test with the medium that suits the valve's service. Both are within our NATA accreditation from 0 to 100,000 kPa.
Hydrostatic · water
Liquid service
Set pressure and seat tightness tested with water on the bench.
NATA: AS 1271 s2.6 and API 527 cl 4
Pneumatic · nitrogen
Gas and vapour service
Set pressure, then seat tightness by bubble count.
NATA: AS 1271 s3.4 and API 527 cl 2 & 5
Workshop test bench
Metrus PK2 bench, DN25 to DN400.
Our Metrus PK2 test bench in the Darwin workshop clamps flanged valves from DN25 to DN400 (1 to 16 inch) and takes screwed valves too. Set pressure and seat tightness are tested with water or nitrogen and read on calibrated gauges.
The standard claw clamps the inlet flange on a 300 mm reach and suits most valves. The T-claw has a tighter 220 mm reach and holds about double the pressure on the same flange size. The limits below are the maximum test pressure for each flange size.
Maximum test pressure by flange size, from the bench’s clamping plate.
How a test runs
As found, adjusted, tested, certified.
- 01
Record
Nameplate, set pressure and condition as received.
- 02
As found
Pressure raised until the valve lifts. Set pressure recorded.
- 03
Adjust
Reset to the nameplate by our PRD technicians if it’s out.
- 04
Seat tightness
Held below set and checked for leakage.
- 05
Certify
As-left results on a certificate for every valve.
Mobile test unit
We bring the test bench to your site.
Our mobile test unit runs on nitrogen and tests flanged and screwed valves where they’re removed, read on a calibrated digital master gauge. No freight to a workshop and back.
Seat tightness by bubble count
With the valve held below its set pressure, the outlet is piped to a tube under water and the bubbles are counted for a minute. The count is checked against the API 527 limit for the valve’s set pressure and orifice. Soft-seated valves are tested to zero bubbles.

Valves we test
Flanged and screwed, process and utility.
Workshop
Flanged PSVs
Process and plant safety valves, DN25 to DN400 on the bench.
Workshop or site
Screwed PRVs
Air receivers, compressors and small vessels.
People
ASME PRD technicians
Certified for the inspection, testing, maintenance and certification of pressure relieving devices.
If it fails
Replacement valves
We can supply a replacement valve or spring so the equipment goes back into service.
What you get
A certificate for every valve, as found and as left.
- As-found and as-left set pressure
- Seat tightness result
- A NATA-endorsed certificate for tests within our scope
- Master gauge ID and calibration details
- A clear pass, reset or fail call
What we need from you
Two things.
- A valve list: tag, size, connection and set pressure
- The service: gas, vapour or liquid
Pressure testing the system as well? See hydrostatic testing.
Brochure
PRV and PSV testing
Relief valve testing on the workshop bench or our mobile unit.
4 pages · PDF 0.8 MB
Get in touch
Relief valves due for testing?
Swift reporting, round the clock.